Abstract:
The energy and global warming crises have drawn renewed interests to thermally driven cooling
systems from the air conditioning and process cooling fraternities. The early development of an
absorption cycle dates back to the 1700’s. It was known that ice could be produced by an
evaporation of pure water from a vessel contained within an evacuated container in the presence of
sulfuric acid. In 1810, ice could be made from water in a vessel, which was connected to another
vessel containing sulfuric acid. As the acid absorbed water vapor, causing a reduction of
temperature, layers of ice were formed on the water surface. The major problems of this system
were corrosion and leakage of air into the vacuum vessel. In 1859, Ferdinand Carre introduced a
novel machine using water/ammonia as the working fluid. The lithium bromide-water absorption
chiller is one of the favorite due to the following specific reasons: (a) it can be thermally driven by
gas, solar energy, and geothermal energy as well as waste heat, which help to substantially reduce
carbon dioxide emission; (b) its use of water as a refrigerant;(c) it is quiet, durable and cheap to
maintain, being nearly void of high speed moving parts; (d) its vacuumed operation renders it
amenable to scale up applications. The internal operation of a lithium bromide-water absorption
chiller is intimately influenced by the pressures and concentrations of its working fluid. In its most
basic form, there are four intrinsic components to a lithium bromide-water absorption chiller: an
evaporator, a generator, an absorber and a condenser. In the generator refrigerant vapour is
thermally desorbed from the solution, which is then condensed in the condenser. The liquid
refrigerant in the condenser is throttled and sent to the evaporator where cooling is provided. In the
evaporator, the liquid refrigerant vaporizes and the vapour is absorbed by the solution which is
actively cooled in the absorber. The refrigerant rich solution is pumped to the generator for
generation, while the resultant refrigerant-weak solution is throttled back to the absorber to absorb
the refrigerant vapour coming from the evaporator. To improve the system efficiency, a solution
heat exchanger is introduced into the solution circuit to recover the energy of the refrigerant-weak
solution when it is throttled from the generator to the absorber. The performance index of an
absorption chiller is termed the Coefficient of Performance (COP) and is generally defined as the
ratio of cooling output at the evaporator to the heat input to the generator. The aim of this paper is
to study the absorption refrigeration. A number of absorption refrigeration systems are examined
and discussed. The study shows that double-effect absorption systems using lithium bromide/water
seem to be the only high performance system which is available commercially It must be noted that,
when the number of effects increase, COP of each effect will not be as high as that for a singleeffect
system. Moreover, the higher number of effect leads to more system complexity